- HVAC SYSTEMS TESTING, ADJUSTING & BALANCING
- THIRD EDITION — AUGUST, 2002
- FOREWORD
- TASK FORCE
- NOTICE TO USERS OF THIS PUBLICATION
- TABLE OF CONTENTS [Go to Page]
- CHAPTERS
- TABLES
- FIGURES
- CHAPTER 1 INTRODUCTION [Go to Page]
- 1.1 INTRODUCTION TO TAB WORK
- 1.2 THE TAB TECHNICIAN/TEAM
- 1.3 GENERAL REQUIREMENTS
- CHAPTER 2 HVAC FUNDAMENTALS [Go to Page]
- 2.1 HEAT FLOW
- FIGURE 2-1 HEAT TRANSFER BY CONDUCTION AND RADIATION
- FIGURE 2-2 CONVECTION HEAT TRANSFER
- FIGURE 2-3 COUNTER FLOW AIR-STREAMS
- FIGURE 2-4 PARALLEL FLOW AIR- STREAMS
- FIGURE 2-5 CROSS-FLOW AIR-STREAMS
- FIGURE 2-6 PARALLEL AND COUNTERFLOW HEAT TRANSFER CURVES
- 2.2 PSYCHROMETRICS
- FIGURE 2-7 PSYCHROMETRIC CHART (I-P)
- FIGURE 2-8 PSYCHROMETRIC CHART - TYPICAL CONDITION POINTS (SI)
- FIGURE 2-9 PSYCHROMETRIC CHART - TYPICAL CONDITION POINTS
- FIGURE 2-10 SENSIBLE HEATING AND COOLING (I-P)
- FIGURE 2-11 HUMIDIFICATION AND DEHUMIDIFICATION (I-P)
- FIGURE 2-12 PSYCHROMETRIC CHART - PROCESSES
- FIGURE 2-13 COOLING AND DEHUMIDIFYING (I-P)
- FIGURE 2-14 HEATING AND HUMIDIFICATION
- FIGURE 2-15 MIXING OF TWO AIRSTREAMS (SI)
- 2.3 FLUID MECHANICS
- FIGURE 2-16 TANK STATIC HEAD
- FIGURE 2-17 VELOCITY PROFILE
- FIGURE 2-18 PRESSURE CHANGES DURING FLOW IN DUCTS
- FIGURE 2-19 SAMPLE FITTING LOSS COEFFICIENT TABLE
- FIGURE 2-20 PUMP WITH STATIC HEAD AND SUCTION HEAD
- FIGURE 2-21 PUMP WITH SUCTION LIFT
- CHAPTER 3 ELECTRICAL EQUIPMENT AND CONTROLS [Go to Page]
- 3.1 ELECTRICAL SYSTEMS
- 3.2 ELECTRICAL SERVICES
- FIGURE 3-1 SERIES-PARALLEL CIRCUIT
- FIGURE 3-2 SINGLE-PHASE AC SERVICE
- FIGURE 3-3 CURRENT AND VOLTAGE-TIME CURVES AND POWER FACTOR
- FIGURE 3-4 220-VOL T THREE-WIRE DELTA THREE-PHASE CIRCUIT
- FIGURE 3-5 220-VOL T DELTA THREE-PHASE CIRCUIT WITH 110-VOL T SINGLE-PHASE SUPPLY
- FIGURE 3-6 120/208-VOL T FOUR-WIRE WYE CIRCUIT
- 3.3 TRANSFORMERS
- FIGURE 3-7 TRANSFORMER WITH TAPPED SECONDARY
- 3.4 MOTORS
- FIGURE 3-8 TYPICAL PERFORMANCE OF STANDARD SQUIRREL CAGE INDUCTION MOTORS
- 3.5 MOTOR CONTROLS
- 3.6 VARIABLE FREQUENCY DRIVES
- FIGURE 3-9 INTERLOCKED STARTERS WITH CONTROL TRANSFORMERS
- FIGURE 3-10 VFD ADDED TO EXIST-ING AIR HANDLING UNIT
- CHAPTER 4 TEMPERATURE CONTROL [Go to Page]
- 4.1 AUTOMATIC TEMPERATURE CONTROL SYSTEMS
- 4.2 CONTROL LOOPS
- FIGURE 4-1 VALVE THROTTLING CHARACTERISTIC COMPARISON
- FIGURE 4-2 ATC VALVE ARRANGEMENTS
- FIGURE 4-3 TYPICAL MULTIBLADE DAMPERS
- 4.3 CONTROL DIAGRAMS
- 4.4 CONTROL RELATIONSHIPS
- 4.5 ATC SYSTEM ADJUSTMENT
- 4.6 TAB/ATC RELATIONSHIP
- 4.7 CENTRALIZED CONTROL SYSTEMS
- FIGURE 4-4 DESKTOP COMPUTER DISPLAYING STATUS OF BUILDING HVAC SYSTEMS
- FIGURE 4-5 FUNCTIONAL BLOCK DIAGRAM A CENTRALIZED COMPUTER CONTROL SYSTEM
- FIGURE 4-6 HVAC CONTROLS PANEL WITH ORIGINAL PNEUMATIC CONTROLS
- FIGURE 4-7 THE SAME HVAC CONTROL PANEL AFTER UPGRADING TO DIRECT DIGITAL CONTROL (DDC).
- FIGURE 4-8 PORTABLE COMPUTER PLUGGED INTO ELECTRONIC WALL THERMOSTAT
- CHAPTER 5 FANS [Go to Page]
- 5.1 FAN CHARACTERISTICS
- FIGURE 5-1 CENTRIFUGAL FAN COMPONENTS
- FIGURE 5-2 CHARACTERISTIC CURVES FOR FC FANS
- FIGURE 5-3 CHARACTERISTIC CURVES FOR BI FANS
- FIGURE 5-4 CHARACTERISTIC CURVES FOR AIR FOIL
- FIGURE 5-5 AXIAL FAN COMPONENTS
- FIGURE 5-6 CHARACTERISTIC CURVES FOR PROPELLER FANS
- FIGURE 5-7 CHARACTERISTIC CURVES FOR VANEAXIAL FANS (HIGH PERFORMANCE)
- FIGURE 5-8 TUBULAR CENTRIFUGAL FAN
- FIGURE 5-9 CHARACTERISTIC CURVES FOR TUBULAR CENTRIFUGAL FANS
- 5.2 FAN CONSTRUCTION
- FIGURE 5-10 FAN CLASS STAN-DARDS (I-P) (SW BI FANS)
- FIGURE 5-11 FAN CLASS STAN- DARDS (SI) (SW BI FANS)
- FIGURE 5-12 DRIVE ARRANGEMENTS FOR CENTRIFUGAL FANS
- Table 5-1 Typical Fan Rating Table
- FIGURE 5-13 ARRANGEMENT 1 IN-LINE FANS
- FIGURE 5-14 ARRANGEMENT 4 IN-LINE FANS
- FIGURE 5-15 ARRANGEMENT 9 IN-LINE FANS
- FIGURE 5-16 CENTRIFUGAL FAN MOTOR LOCATIONS
- 5.3 FAN AIRFLOW AND PRESSURES
- FIGURE 5-17 DIRECTION OF ROTATION AND DISCHARGE
- FIGURE 5-18 FAN TOTAL PRESSURE (TP)
- FIGURE 5-19 FAN STATIC PRES-SURE (SP)
- FIGURE 5-20 FAN VELOCITY PRESSURE (V P )
- FIGURE 5-21 TIP SPEED
- 5.4 FAN/SYSTEM CURVE RELATIONSHIP
- FIGURE 5-22 SYSTEM RESISTANCE CURVE
- FIGURE 5-23 OPERATING POINT
- FIGURE 5-24 VARIATIONS FROM DESIGN AIR SHORTAGE
- FIGURE 5-25 FAN LAW - RPM CHANGE
- FIGURE 5-26 EFFECT OF DENSITY CHANGE (CONSTANT VOLUME)
- FIGURE 5-27 EFFECT OF DENSITY CHANGE (CONSTANT STATIC PRESSURE)
- 5.5 FAN CAPACITY RATINGS
- FIGURE 5-28 AMCA FAN TEST - PITOT TUBE
- FIGURE 5-29 EFFECT OF DENSITY CHANGE (CONSTANT MASS FLOW)
- FIGURE 5-30 EFFECTS OF SYSTEM EFFECT
- FIGURE 5-31 FAN OUTLET EFFECTIVE DUCT LENGTH
- FIGURE 5-32 NON-UNIFORM FLOW CONDITIONS INTO FAN INLET
- CHPATER 6 AIR DISTRIBUTION AND DEVICES [Go to Page]
- 6.1 AIR TERMINAL BOXES
- FIGURE 6-1 CONSTANT VOLUME FAN-POWERED BOX
- 6.2 VARIABLE AIR VOLUME (VAV) TERMINAL BOXES
- FIGURE 6-2 BYPASS-TYPE FAN-POWERED BOX
- 6.3 OTHER AIRFLOW DEVICES
- FIGURE 6-3 MULTIBLADE VOLUME DAMPERS
- FIGURE 6-4 FLOW CHARACTERISTICS FOR A PARALLEL OPERATING DAMPER
- FIGURE 6-5 FLOW CHARACTERISTICS FOR AN OPPOSED OPERATING DAMPER
- 6.4 AIR DISTRIBUTION BASICS
- Table 6-1 Typical Ratios of Damper to System Resistance for Flow Characteristic Curve
- FIGURE 6-6 VOLUME DAMPERS
- FIGURE 6-7 SURFACE (COANDA) EFFECT
- 6.5 ROOM AIR DISTRIBUTION
- FIGURE 6-8 SOME ELEMENTS AFFECTING BODY HEAT LOSS
- FIGURE 6-9 FOUR ZONES IN JET EXPANSION
- FIGURE 6-10 TYPICAL SUPPLY OUTLETS
- Table 6-2 Guide to Use of Various Outlets
- Table 6-3 Recommended Return Air Inlet Face Velocities
- Table 6-4 Air Outlets and Diffusers Total Pressure Loss Average—in. wg (Pa)
- Table 6-5 Supply Registers Total Pressure Loss Average—in. wg (Pa)
- Table 6-6 Return Registers Total Pressure Loss Average—in. wg (Pa)
- CHAPTER 7 AIR SYSTEMS [Go to Page]
- 7.1 INTRODUCTION
- 7.2 TYPES OF AIR SYSTEMS
- FIGURE 7-1 SINGLE DUCT SYSTEM
- FIGURE 7-2 TYPICAL EQUIPMENT FOR SINGLE ZONE DUCT SYSTEM
- FIGURE 7-3 VARIABLE AIR VOLUME (VAV) SYSTEM
- FIGURE 7-4 TERMINAL REHEAT SYSTEM
- FIGURE 7-5 INDUCTION REHEAT SYSTEM
- FIGURE 7-6 DUAL DUCT HIGH VELOCITY SYSTEM
- FIGURE 7-7 MULTI-ZONE SYSTEM
- 7.3 AIR SYSTEM DESIGN
- 7.4 DUCT SIZING EXAMPLES
- FIGURE 7-8 SYSTEM LAYOUT (I-P UNITS)
- FIGURE 7-9 SYSTEM LAYOUT (SI)
- 7.5 SUMMARY
- FIGURE 7-10 FAN DUCT CONNECTIONS
- CHPATER 8 HYDRONIC EQUIPMENT [Go to Page]
- 8.1 PUMPS
- FIGURE 8-1 TYPICAL CENTRIFUGAL PUMP CROSS SECTION
- FIGURE 8-2 DESCRIPTIONS OF CNTRIFUGAL PUMPS USED IN HYDRONIC SYSTEMS
- Table 8-1 Characteristics of Centrifugal Pumps
- Table 8-2 Characteristics of Common Types of Pumps
- FIGURE 8-3 COUPLING ALIGNMENT WITH STRAIGHT EDGE
- FIGURE 8-4 TYPICAL REQUIRED NPSH CURVE
- 8.2 PUMP / SYSTEM CURVE RELATIONSHIP
- FIGURE 8-5 PUMP CURVE FOR 1750 RPM OPERATION
- FIGURE 8-6 TYPICAL DESIGN PUMP SELECTION POINT (FROM ABBREVIATED CURVE)
- FIGURE 8-7 SYSTEM CURVE PLOTTED ON PUMP CURVE
- FIGURE 8-8 TYPICAL OPEN SYSTEMS
- FIGURE 8-9 TYPICAL COOLING TOWER APPLICATION POINT
- FIGURE 8-10 SYSTEM CURVE FOR OPEN CIRCUIT FALSE OPERATING POINT
- FIGURE 8-11 SYSTEM CURVE FOR OPEN CIRCUIT TRUE OPERATING POINT
- FIGURE 8-12 PUMP OPERATING POINTS
- Table 8-3 Flow vs Total Head (Cooling Tower Application)
- FIGURE 8-13 MULTIPLE PUMPS
- FIGURE 8-14 PUMP AND SYSTEM CURVES FOR PARALLEL PUMPING
- 8.3 PUMP INSTALLATION CRITERIA
- FIGURE 8-16 GAGE LOCATION
- FIGURE 8-15 PUMP AND SYSTEM CURVES FOR SERIES PUMPING
- FIGURE 8-17 RELATIVE GAGE ELEVATIONS
- FIGURE 8-18 EFFECT OF VISCOSITY
- 8.4 HYDRONIC HEATING AND COOLING SOURCES
- 8.5 TERMINAL HEATING AND COOLING UNTS
- CHPATER 9 HYDRONIC SYSTEMS [Go to Page]
- 9.1 HYDRONIC SYSTEMS
- FIGURE 9-1 A SERIES LOOP SYSTEM
- FIGURE 9-2 A ONE-PIPE SYSTEM
- FIGURE 9-3 DIRECT RETURN TWO-PIPE SYSTEM
- FIGURE 9-4 REVERSE RETURN TWO-PIPE SYSTEM
- FIGURE 9-5 EXAMPLE OF PRIMARY AND SECONDARY PUMPING CIRCUITS
- FIGURE 9-6 RETURN MIX SYSTEM ROOM UNIT CONTROLS
- FIGURE 9-7 FOUR PIPE SYSTEM ROOM UNIT
- FIGURE 9-8 BOILER PIPING FOR A MULTIPLE-ZONE, MULTIPLE-PURPOSE HEATING SYSTEM
- Table 9-1 Hydronic Trouble Analysis Guide
- 9.2 HYDRONIC SYSTEM DESIGN
- FIGURE 9- 9 WATER COOLED CONDENSER CONNECTIONS FOR CITY WATER
- 9.3 HYDRONIC DESIGN PROCEDURES
- FIGURE 9-10 COOLING TOWER PIPING SYSTEM
- 9.4 STEAM SYSTEMS
- FIGURE 9-11 BASIC PIPING CIRCUITS FOR GRAVITY FLOW OF CONDENSATE
- FIGURE 9-12 BASIC PIPING CIRCUITS FOR MECHANICAL RETURN SYSTEMS
- FIGURE 9-13 TYPICAL TWO-PIPE VACUUM STEAM SYSTEM
- FIGURE 9-14 THERMOSTATIC TRAP
- FIGURE 9-15 INVERTER BUCKET TRAP
- FIGURE 9-16 FLOAT AND THERMOSTATIC TRAP
- FIGURE 9-17 TYPICAL CONNECTIONS TO FINNED TUBE HEATING COLIS
- CHPATER 10 REFERIGERATION SYSTEMS [Go to Page]
- 10.1 REFRIGERATION SYSTEMS
- FIGURE 10-1 REFRIGERANT CYCLE
- 10.2 REFRIGERATION TERMS AND COMPONENTS
- 10.3 SAFETY CONTROLS
- 10.4 OPERATING CONTROLS
- 10.5 REFRIGERANTS
- 10.6 THERMAL BULBS AND SUPERHEAT
- FIGURE 10-2 LOCATIONS OF THERMAL BULBS
- 10.7 COMPRESSOR SHORT CYCLING
- CHAPTER 11 TAB INSTRUMENTS [Go to Page]
- 11.1 INTRODUCTION
- 11.2 AIRFLOW MEASURING INSTRUMENTS
- FIGURE 11-1 U-TUBE MANOMETER EQUIPPED WITH OVER-PRESSURE TRAPS
- FIGURE 11-2 INCLINED-VERTICAL MANOMETER
- FIGURE 11-3 ELECTRONIC/ MULTI-METER
- FIGURE 11-4 PITOT TUBE CONNECTIONS
- FIGURE 11-5 PITOT TUBE
- FIGURE 11-6 MAGNEHELIC GAGE
- FIGURE 11-7 ROTATING VANE ANEMOMETER
- FIGURE 11-8 ELECTRONIC ANALOG ROTATING VANE ANEMOMETER
- FIGURE 11-9 DEFLECTING VANE ANEMOMETER SET
- FIGURE 11-10 THERMAL ANEMOMETER
- FIGURE 11-1 1 FLOW MEASURING HOOD
- Table 11-1 Airflow Measuring Instruments
- 11.3 PRESSURE GAGE, CALIBRATED
- FIGURE 11-12 CALIBRATED PRESSURE GAGES
- Table 11-2 Instruments for Hydronic Balancing
- Table 11-3 Hydronic Measuring Instruments
- FIGURE 11-13 SINGLE GAGE BEING USED TO MEASURE A DIFFERENTIAL PRESSURE
- 11.4 ROTATION MEASURING INSTRUMENTS
- FIGURE 11-14 SINGLE GAGE BEING USED TO MEASURE A DIFFERENTIAL PRESSURE
- FIGURE 11-15 DIFFERENTIAL PRESSURE GAGE
- Table 11-4 Rotation Measuring Instruments
- FIGURE 11-16 CHRONOMETRIC TACHOMETER
- FIGURE 11-17 DIGITAL CONTACT TACHOMETER
- FIGURE 11-18 DIGITAL OPTICAL TACHOMETER
- FIGURE 11-19 STROBOSCOPE
- FIGURE 11-20 MULTI-RANGE, DUAL FUNCTION (OPTICAL/CONTACT TACHOMETER)
- 11.5 TEMPERATURE FUNCTION TACHOMETER MEASURNG INSTRUMENTS
- Table 11-5 Instrumentation for Air & Hydronic Balancing
- Table 11-6 Instruments for Air Balancing
- FIGURE 11-21 GLASS TUBE THERMOMETERS
- FIGURE 11-22 DIAL THERMOMETER
- FIGURE 11-23 THERMOCOUPLE
- FIGURE 11-24 THERMISTOR THERMOMETER
- FIGURE 11-25 INFRARED DIGITAL THERMOMETER
- FIGURE 11-26 RESISTANCE TEMPERATURE DETECTOR
- FIGURE 11-27 ELECTRONIC THERMOMETER
- Table 11-7 Temperature Measuring Instruments
- FIGURE 11-28 SLING PSYCHROMETER
- FIGURE 11-29 DIGITAL PSYCHROMETER
- 11.6 ELECTRICAL MEASURING INSTRUMENTS
- 11.7 COMMUNICATION DEVICES
- FIGURE 11-30 THERMOHYGROMETER
- FIGURE 11-31 CLAMP-ON VOLT AMMETER
- FIGURE 11-32 ACCESSING AUTOMATION SYSTEM WITH LAPTOP COMPUTER
- 11.8 HYDRONIC FLOW MEASURING DEVICES
- FIGURE 11-33 ORIFICE AS A MEASURING DEVICE
- FIGURE 11-34 FLOW METER TYPES
- FIGURE 11-35 ANNULAR FLOW INDICATOR
- FIGURE 11-36 CALIBRATED BALANCING VALVE
- CHAPTER 12 PRELIMINARY TAB PROCEDURES [Go to Page]
- 12.1 INITIAL PLANNING
- 12.2 CONTRACT DOCUMENTS
- 12.3 SYSTEM REVIEW AND ANALYSIS
- FIGURE 12-1 SCHEMATIC DUCT SYSTEM LAYOUT
- 12.4 THE AGENDA
- FIGURE 12-2 INSTRUMENTS SELECTED FOR A SPECIFIC JOB
- 12.5 PLANNING FIELD TAB PROCEDURES
- 12.6 PRELIMINARY FIELD PROCEDURES
- CHAPTER 13 GENERAL AIR SYSTEM TAB PROCEDURES [Go to Page]
- 13.1 BASIC FAN TESTING PROCEDURES
- 13.2 SYSTEM STARTUP
- 13.3 FAN TESTING
- 13.4 DEFICIENCY REVIEW
- 13.5 RETURN AND OUTSIDE AIR SETTINGS
- 13.6 ANALYSIS OF MEASUREMENTS
- 13.7 RECORDING DATA
- 13.8 PROPORTIONAL BALANCING (RATIO) METHOD
- 13.9 PERCENTAGE OF DESIGN AIRFLOW
- FIGURE 13-1 SAMPLE SUPPLY AIR DUCT (PART)
- 13.10 SYSTEM AIRFLOW
- 13.11 BASIC OUTLET BALANCING PROCEDURES
- 13.12 STEPWISE METHOD
- FIGURE 13-2 TYPICAL AIR DIFFUSER CFM MEASUREMENT
- 13.13 FAN ADJUSTMENT
- 13.14 WET COIL CONDITIONS
- 13.15 AIRFLOW TOTALS
- 13.16 EXHAUST FANS
- 13.17 FAN DRIVE ADJUSTMENT
- 13.18 DAMPER ADJUSTMENTS
- 13.19 DUCT TRAVERSES
- FIGURE 13-3 MEASURING EXHAUST AIR VELOCITY ON LAB EXHAUST HOOD WITH SASH HEIGHT
- 13.20 SYSTEM DEFICIENCIES
- 13.21 FUME HOOD EXHAUST BALANCING PROCEDURES
- FIGURE 13-4 EXAMPLE OF EXHAUST HOOD AIR BALANCE LABEL
- 13.22 DUST COLLECTION AND EXHAUST BALANCING PROCEDURES
- FIGURE 13-5 SAMPLE DUST COLLECTION EXHAUST SYSTEM
- 13.23 AIR FLOW MEASUREMENTS ON DISCHARGE STACKS
- 13.24 INDUSTRIAL VENTILATION
- 13.25 SELECTION OF INSTRUMENTS
- CHPATER 14 TAB PROCEDURES FOR SPECIFIC AIR SYSTEMS [Go to Page]
- 14.1 INTRODUCTION
- 14.2 VARIABLE AIR VOLUME (VAV) SYSTEMS
- FIGURE 14-1 TYPICAL VARIABLE AIR VOLUME (VAV) SYSTEM
- FIGURE 14-2 OPEN LOOP FAN VOLUME CONTROL
- FIGURE 14-3 CLOSED LOOP FAN VOLUME CONTROL
- FIGURE 14-4 FAN AND SYSTEM CURVES, CONSTANT SPEED FAN
- FIGURE 14-5 FAN AND SYSTEM CURVES, VARIABLE SPEED FAN
- FIGURE 14-6 SERIES FAN POWERED
- FIGURE 14-7 PARALLEL FAN POWERED VAV UNIT
- FIGURE 14-8 PAPER STRIP AT VAV BOX RETURN BEFORE BALANCING
- FIGURE 14-9 PAPER STRIP AT VAV BOX AFTER BALANCING
- FIGURE 14-10 CONSTANT FAN VAV BOX
- FIGURE 14-11 INTERMITTENT FAN VAV BOX (PARALLEL) CYCLE
- 14.3 MULTI-ZONE SYSTEMS
- 14.4 INDUCTION UNIT SYSTEMS
- 14.5 DUAL DUCT SYSTEMS
- FIGURE 14-12 MULTI-ZONE SYSTEM
- FIGURE 14-13 DUAL DUCT SYSTEM
- 14.6 SPECIAL EXHAUST AIR SYSTEMS
- FIGURE 14-14 INDUCTION UNIT SYSTEM
- 14.7 PROCESS EXHAUST AIR SYSTEMS
- CHAPTER 15 HYDRONIC SYSTEM TAB PROCEDURES [Go to Page]
- 15.1 HYDRONIC SYSTEM MEASUREMENT METHODS
- FIGURE 15-1 HYDRONIC FLOW MEASUREMENT
- FIGURE 15-2 EXTERNAL ULTRASONIC FLOW SENSOR ON PIPE WITH INSULATION REMOVED
- FIGURE 15-3 ULTRASONIC FLOW METER
- 15.2 BASIC HYDRONIC SYSTEM PROCEDURES
- 15.3 PIPING SYSTEM BALANCING
- 15.4 BALANCING SPECIFIC SYSTEMS
- 15.5 VARIABLE VOLUME FLOW
- FIGURE 15-4 EFFECTS OF VARIATION ON HEAT TRANSFER 20 FLOW F (11 C) .t AT 200 F (93 C)
- FIGURE 15-5 PERCENT VARIATION TO MAINTAIN 90% TERMINAL HEAT TRANSFER
- Table 15-1 Load-Flow Variations
- FIGURE 15-6 CHILLED WATER TERMI-NAL FLOW VERSUS HEAT TRANSFER
- FIGURE 15-7 PUMP WITH VARIABLE SPEED DRIVE
- 15.6 PRIMARY-SECONDAR Y SYSTEMS
- 15.7 SUMMER-WINTER SYSTEMS
- FIGURE 15-8 EXAMPLE OF PRIMARY AND SECONDARY PUMPING CIRCUITS
- FIGURE 15-9 SUMMER-WINTER SYSTEMS
- CHAPTER 16 TAB REPORT FORMS [Go to Page]
- 16.1 PREPARING TAB REPORT FORMS
- 16.2 DESCRIPTION OF USE
- System Diagram—TAB 1-02
- Air Apparatus Test Report TAB 2-02
- Apparatus Coil Test Report TAB 3-02
- Gas/Oil Fired Heat Apparatus Test Report—TAB 4-02
- Electronic Coil/Duct Heater Test Report—TAB 5-02
- Fan Test Report—TAB 6-02
- Rectangular Duct Traverse Report— TAB 7-02
- Round Duct Traverse Report— TAB 8-02
- Air Outlet Test Report (Includes TAB 9A-02, TAB 9B-02 AND TAB 9C-02)
- Terminal Unit Coil Check Report— TAB 11-02
- Packaged Chiller Test Report— TAB 12-02
- Package Rooftop/Heat Pump/Air Conditioning Unit Test Report— TAB 13-02
- Compressor and/or Condenser Test Report—TAB 14-02
- Cooling Tower or Evaporative Condenser Test Report—TAB 15-02
- Heat Exchanger/Converter Test Report—TAB 16-02
- Pump Test Report—TAB 17-02
- Balance Valve/Flow Meter Test Report—TAB 18-02
- Boiler Test Report—TAB 19-02
- Instrument Calibration Report— TAB 20-02
- TAB REPORT FORMS [Go to Page]
- TAB 1-02
- TAB 2-02
- TAB 3-02
- TAB 4-02
- TAB 5-02
- TAB 6-02
- TAB 7-02
- TAB 7-02 (Cont.)
- TAB 8-02
- TAB 8-02 (Cont.)
- TAB 9A-02
- TAB 9B-02
- TAB 9C-02
- TAB 10-02
- TAB 11-02
- TAB 12-02
- TAB 13-02
- TAB 14-02
- TAB 15-02
- TAB 16-02
- TAB 17-02
- TAB 18-02
- TAB 19-02
- TAB 20-02
- APPENDIX A DUCT DESIGN TABLES & CHARTS [Go to Page]
- FIGURE A-1 DUCT FRICTION LOSS CHART (I-P)
- FIGURE A-2 DUCT FRICTION LOSS CHART (SI)
- Table A-1 Duct Material Roughness Factors
- FIGURE A-3 DUCT FRICTION LOSS CORRECTION FACTORS
- Table A-2 Circulation Equivalents of Rectangular Ducts for Equal Friction and Capacity (I-P) (2) Dimensions in Inches
- Table A-2 Circulation Equivalents of Rectangular Ducts (continued)
- Table A-3 Circular Equivalents of Rectangular Ducts for Equal Friction and Capacity (SI) (2) Dimensions in mm
- Table A-3 Circular Equivalents of Rectangular Ducts for Equal Friction and Capacity (SI) (2) Dimensions in mm (continued)
- Table A-4 Velocities/Velocity Pressures (I-P)
- FIGURE A-4 VELOCITIES/VELOCITY PRESSURES (I-P)
- Table A-5 Velocities/Velocity Pressures (SI)
- Table A-6 Angular Conversion
- Table A-7 Loss Coefficients for Straight-Through Flow
- FIGURE A-5 AIR DENSITY FRICTION CHART CORRECTION FACTORS
- FIGURE A-6 LOUVER VELOCITY
- Table A-8 Recommended Criteria for Louver Sizing
- Table A-9 Typical Design Velocities for Duct Components
- FITTING LOSS COEFFICIENT TABLES
- Table A-10 Elbow Loss Coefficients
- Table A-10 Elbow Loss Coefficients (continued)
- Table A-10 Elbow Loss Coefficients (continued)
- Table A-11 Transition Loss Coefficients
- Table A-11 Transition Loss Coefficients (continued)
- Table A-12 Rectangular Branch Connection Loss Coefficients
- Table A-12 Rectangular Branch Connection Loss Coefficients (continued)
- Table A-12 Rectangular Branch Connection Loss Coefficients (continued)
- Table A-12 Rectangular Branch Connection Loss Coefficients (continued)
- Table A-13 Round Branch Connection Loss Coefficients
- Table A-13 Round Branch Connection Loss Coefficients (continued)
- Table A-13 Round Branch Connection Loss Coefficients (continued)
- Table A-13 Round Branch Connection Loss Coefficients (continued)
- Table A-14 Miscellaneous Fitting Coefficients
- Table A-14 Miscellaneous Fitting Coefficients (continued)
- Table A-14 Miscellaneous Fitting Coefficients (continued)
- Table A-14 Miscellaneous Fitting Coefficients (continued)
- HVAC EQUATIONS (I-P)
- Air Equations (I-P)
- Fan Equations (I-P)
- Pump Equations (I-P)
- Hydronic Equivalents (I-P)
- Hydronic Equations (I-P)
- Electric Equations (I-P)
- Table A-15 Converting Pressure In Inches of Mercury to Feet of Water at Various Water Temperatures
- Table A-16 Air Density Correction Factors (I-P)
- HVAC EQUATIONS (SI)
- Air Equations (SI)
- Fan Equations (SI)
- Pump Equations (SI)
- Hydronic Equations (SI)
- Table A-17 Air Density Correction Factors (SI)
- SI UNITS AND EQUIVALENTS
- Table A-18 SI Units (Basic and Derived)
- Table A-19 SI Equivalents
- Table A-20 Sound Design Equations
- Table A-20 Sound Design Equations (continued)
- FITTING EQUIVALENTS (WATER)
- Table A-21 Equivalent Length in Feet of Pipe for 90 Elbows
- Table A-22 Equivalent Length in Meters of Pipe for 90 Elbows
- Table A-23 Iron and Copper Elbow Equivalents
- FIGURE A-7 ELBOW EQUIVALENTS OF TEES AT VARIOUS FLOW CONDITIONS
- Table A-24 Properties of Saturated Steam (I-P)
- Table A-25 Properties of Saturated Steam (SI)
- STEAM PIPING (I-P)
- Table A-26 Steam Piping (I-P) Flow Rate of Steam in Schedule 40 Pipe at Initial Saturation Pressure of 3.5 and 12 psig
- Table A-27 Comparative Capacity of Steam Lines at Various Pitches for Steam and Condensate Flowing in Opposite Directions
- Table A-28 Pressure Drops In Common Use for Sizing Steam Pipe (For Corresponding Initial Steam Pressure)
- Table A-29 Length in Feet of Pipe to be Added to Actual Length of Run — Owing to Fittings — to Obtain Equivalent Length
- Table A-30 Steam Pipe Capacities for Low Pressure Systems (For Use on One-Pipe Systems or Two-Pipe Systems in which Condensate Flows Against the Steam Flow)
- Table A-31 Return Main and Riser Capacities for Low-Pressure Systems—Pounds per Hour
- STEAM PIPING (SI)
- Table A-32 Flow Rate in kg/h of Steam in Schedule 40 Pipe at Initial Saturation Pressure of 15 and 85 kPa Above Atmospheric
- Table A-33 Comparative Capacity of Steam Lines at Various Pitches for Steam and Condensate Flowing in Opposite Directions
- Table A-34 Equivalent Length of Fittings to be Added to Pipe Run
- Table A-35 Steam Pipe Capacities for Low-Pressure Systems
- Table A-36 Return Main and Riser Capacities for Low-Pressure Systems — kg/h
- Sample Specification for Testing, Adjusting and Balancing
- REFERENCES
- GLOSSARY [Go to Page]
- -A -
- -B -
- -C -
- -D -
- -E -
- -F -
- -G
- -H -
- -I -
- -J -
- -K -
- -L -
- -M -
- -N -
- -O -
- -P -
- -R -
- -S -
- -T -
- -U -
- -V -
- -W -
- -Z -
- INDEX [Go to Page]